View Issue Details

IDProjectCategoryView StatusLast Update
000302910000-009: Alarms and ConditionsSpecpublic2015-04-14 16:44
ReporterKarl Deiretsbacher Assigned ToPaul Hunkar  
PrioritynormalSeverityminorReproducibilityhave not tried
Status closedResolutionfixed 
Target Version1.03Fixed in Version1.03 
Summary0003029: CertificateExpiration Type shall be sub-type of OffNormalAlarmType
Description

With this change the CertificateExpiration has an activeState.

TagsNo tags attached.
Commit Version
Fix Due Date

Relationships

related to 0003035 closedRandy Armstrong NodeSets, XSDs and Generated Code CertificateExpiration Type shall be sub-type of OffNormalAlarmType 

Activities

Paul Hunkar

2015-04-14 15:27

developer   ~0006008

Moved to be under SystemOffNormalAlarmType (which is what was discussed in the call)

Jim Luth

2015-04-14 16:43

administrator   ~0006013

During review we added a Duration to allow the alarm to trigger at something other than the 2 week default

Issue History

Date Modified Username Field Change
2015-04-07 15:45 Karl Deiretsbacher New Issue
2015-04-07 15:55 Karl Deiretsbacher Assigned To => Paul Hunkar
2015-04-07 15:55 Karl Deiretsbacher Status new => assigned
2015-04-14 15:27 Paul Hunkar Note Added: 0006008
2015-04-14 15:27 Paul Hunkar Status assigned => resolved
2015-04-14 15:27 Paul Hunkar Resolution open => fixed
2015-04-14 16:43 Jim Luth Note Added: 0006013
2015-04-14 16:43 Jim Luth Status resolved => closed
2015-04-14 16:43 Jim Luth Fixed in Version => 1.03
2015-04-14 16:44 Jim Luth Issue cloned: 0003035
2015-04-14 16:44 Jim Luth Relationship added related to 0003035
2015-04-14 16:44 Jim Luth Target Version => 1.03
2015-04-14 16:44 Jim Luth Description Updated