Summary0004792: Abnormal Situation Management / Situational Awareness and the OPC UA Alarm Model
Description

Modern operator interfaces use techniques originally described in the ASM's Guidelines (Effective Console Operator HMI Design Practices (ISBN: 978-1514203859)) and elaborated in High Performance HMI Handbook (https://www.amazon.com/High-Performance-HMI-Handbook/dp/0977896919) depend on consolidating alarm state.

The current representation of alarms does a fine job of support a "Current Alarm Display" and it lacks the ability to do alarm consolidation / roll-up.

For example, an object at the lowest level may have multiple alarms of different types and severities. A mechanism to summarize them is needed for Situational Awareness graphics.

Likewise, a given object, which may consist of other objects with alarms), should be able to not only have its own alarms, but also represent the alarm state of the objects that compose it.

I discussed this at the OPAF meeting with Paul Hunkar and Jeff Harding and there was agreement that the OPC Foundation should give this consideration.

Steps To Reproduce

N/A

Additional Information

N/A

TagsNo tags attached.
Commit Version
Fix Due Date

Activities

Alex Johnson

2019-07-05 18:29

reporter   ~0010464

Continuing my study of FF Alarming vs. OPC UA alarming, I found that FF has a rather complex parameter - ALARM_STA, see FF-890 Section 4.4.3.12 - that can represent the current state of 16 process alarms, i.e., it is an alarm summary in the block. For each of the 16 alarms, it can retain/store the current alarm state, the state of acknowledgement, the state of reporting, and the disabled state.

Paul Hunkar

2020-11-19 19:51

developer   ~0013281

Last edited: 2022-02-21 05:43

from other discussion it may also be import to show the highest priority and highest unacked priority in the summary variable (probably need to define an interface that can be added to anything that summaries what is available in the hierarchy below the object that added the interface (also need to consider a variable also) - note: hierarchy would require a notifier hierarchy

Paul Hunkar

2022-04-26 03:34

developer   ~0016624

Added a new section describing an AlarmStateVariableType, that would provide an alarm summary.

Jim Luth

2022-05-17 15:41

administrator   ~0016721

Agreed to changes edited in Telecon.

Issue History

Date Modified Username Field Change
2019-06-21 22:54 Alex Johnson New Issue
2019-06-22 15:19 Jim Luth Severity major => feature
2019-06-22 15:20 Jim Luth Target Version => 1.05
2019-06-22 15:21 Jim Luth Assigned To => Paul Hunkar
2019-06-22 15:21 Jim Luth Status new => assigned
2019-07-05 18:29 Alex Johnson Note Added: 0010464
2019-12-26 05:56 Paul Hunkar Description Updated
2020-11-19 19:51 Paul Hunkar Note Added: 0013281
2022-02-21 05:43 Paul Hunkar Note Edited: 0013281
2022-04-26 03:34 Paul Hunkar Status assigned => resolved
2022-04-26 03:34 Paul Hunkar Resolution open => fixed
2022-04-26 03:34 Paul Hunkar Fixed in Version => 1.05.02
2022-04-26 03:34 Paul Hunkar Note Added: 0016624
2022-05-17 15:41 Jim Luth Status resolved => closed
2022-05-17 15:41 Jim Luth Fixed in Version 1.05.02 => 1.05.02 RC1
2022-05-17 15:41 Jim Luth Note Added: 0016721