View Issue Details

IDProjectCategoryView StatusLast Update
000769710000-015: SafetySpecpublic2022-03-30 07:35
ReporterChristian Eitner Assigned ToChristian Eitner  
PriorityhighSeveritymajorReproducibilityalways
Status closedResolutionopen 
Product Version1.05.00 
Target Version1.05.02 RC1 
Summary0007697: SafetyConsumer: Timeout Errors Lead to Unrecoverable De-Synchronisation of ResponseSPDU MNR
Description
  • variable prevMNR_i serves to identify repeated ResponseSPDUs
  • but it is also incremented in case of WDTimeout, i.e., without a ResponseSPDU having been received
  • this leads to the currently valid ResponseSPDU generating an ID error, from which there is no recovery
Additional Information

fixed with draft version 2022-02-22 OPC 10000-15 - UA Specification Part 15 - Safety 1.05.01.docx

TagsNo tags attached.
Commit Version

Activities

There are no notes attached to this issue.

Issue History

Date Modified Username Field Change
2022-02-04 08:49 Christian Eitner New Issue
2022-02-04 08:49 Christian Eitner Status new => assigned
2022-02-04 08:49 Christian Eitner Assigned To => Christian Eitner
2022-02-23 08:39 Christian Eitner Status assigned => resolved
2022-02-23 08:39 Christian Eitner Additional Information Updated
2022-02-24 16:47 Christian Eitner Status resolved => closed
2022-03-11 14:19 Christian Eitner Target Version 1.05.01 RC1 => ?.??
2022-03-30 07:35 Christian Eitner Target Version ?.?? => 1.05.02 RC1