View Issue Details

IDProjectCategoryView StatusLast Update
000809230081: PADIMImplementation Bugpublic2022-10-13 07:09
ReporterReiner Bühler Assigned ToReiner Bühler  
PrioritynormalSeverityminorReproducibilityalways
Status resolvedResolutionopen 
Summary0008092: Mandatory nodes missing in PA-DIM nodeset 1.0.2.
Description

Some mandatory nodes are missing in the PA-DIM nodeset 1.0.2.

TagsNo tags attached.

Activities

Reiner Bühler

2022-07-01 16:45

manager   ~0017081

The following mandatory nodes are missing in the nodeset 1.0.2:

  • SignalSetType.<SignalIdentifier>.SignalTag
  • TemperatureMeasurementVariableType.SensorType.EnumDictionaryEntries
  • TemperatureMeasurementVariableType.SensorType.EnumValues
  • TemperatureMeasurementVariableType.SensorType.ValueAsDictionaryEntries
  • TemperatureMeasurementVariableType.SensorType.ValueAsText
  • TemperatureMeasurementVariableType.SensorConnection.EnumDictionaryEntries
  • TemperatureMeasurementVariableType.SensorConnection.EnumValues
  • TemperatureMeasurementVariableType.SensorConnection.ValueAsDictionaryEntries
  • TemperatureMeasurementVariableType.SensorConnection.ValueAsText
  • TemperatureMeasurementVariableType.SensorReference.EnumDictionaryEntries
  • TemperatureMeasurementVariableType.SensorReference.EnumValues
  • TemperatureMeasurementVariableType.SensorReference.ValueAsDictionaryEntries
  • TemperatureMeasurementVariableType.SensorReference.ValueAsText
  • FlowMeasurementVariableType.FlowDirection.EnumDictionaryEntries
  • FlowMeasurementVariableType.FlowDirection.EnumValues
  • FlowMeasurementVariableType.FlowDirection.ValueAsDictionaryEntries
  • FlowMeasurementVariableType.FlowDirection.ValueAsText
  • ControlVariableType.OperatingDirection.EnumDictionaryEntries
  • ControlVariableType.OperatingDirection.EnumValues
  • ControlVariableType.OperatingDirection.ValueAsDictionaryEntries
  • ControlVariableType.OperatingDirection.ValueAsText
  • ControlVariableType.ActuatorType.EnumDictionaryEntries
  • ControlVariableType.ActuatorType.EnumValues
  • ControlVariableType.ActuatorType.ValueAsDictionaryEntries
  • ControlVariableType.ActuatorType.ValueAsText
  • TwoStateDiscreteSignalType.TwoStateDiscreteSignal.FalseState
  • TwoStateDiscreteSignalType.TwoStateDiscreteSignal.TrueState
  • MultiStateDiscreteSignalType.MultiStateDiscreteSignal.EnumDictionaryEntries
  • MultiStateDiscreteSignalType.MultiStateDiscreteSignal.EnumValues
  • MultiStateDiscreteSignalType.MultiStateDiscreteSignal.ValueAsText
  • AnalogSignalType.AnalogSignal.EngineeringUnits
  • AnalogSignalType.AnalogSignal.EURange
  • ControlSignalType.ControlSignal.ActuatorType
  • ControlSignalType.ControlSignal.EngineeringUnits
  • ControlSignalType.ControlSignal.EURange
  • ControlSignalType.ControlSignal.OperatingDirection
  • ControlSignalType.ControlSignal.Setpoint
  • ControlSignalType.ControlSignal.ActuatorType.EnumDictionaryEntries
  • ControlSignalType.ControlSignal.ActuatorType.EnumValues
  • ControlSignalType.ControlSignal.ActuatorType.ValueAsDictionaryEntries
  • ControlSignalType.ControlSignal.ActuatorType.ValueAsText
  • ControlSignalType.ControlSignal.OperatingDirection.EnumDictionaryEntries
  • ControlSignalType.ControlSignal.OperatingDirection.EnumValues
  • ControlSignalType.ControlSignal.OperatingDirection.ValueAsDictionaryEntries
  • ControlSignalType.ControlSignal.OperatingDirection.ValueAsText

Reiner Bühler

2022-07-01 16:50

manager   ~0017082

A corrected nodeset has been created with version 1.0.3 and publication date 2022-06-27. This nodeset includes all nodes missed in the nodeset 1.0.2. It will be published via the normal OPC Foundation process.

Issue History

Date Modified Username Field Change
2022-07-01 16:41 Reiner Bühler New Issue
2022-07-01 16:41 Reiner Bühler Status new => assigned
2022-07-01 16:41 Reiner Bühler Assigned To => Reiner Bühler
2022-07-01 16:45 Reiner Bühler Note Added: 0017081
2022-07-01 16:50 Reiner Bühler Note Added: 0017082
2022-10-13 07:09 Reiner Bühler Status assigned => resolved