View Issue Details

IDProjectCategoryView StatusLast Update
000922130120: IO-LinkDocumentation Erratapublic2024-02-16 10:29
ReporterTobias Gürtler Assigned ToTobias Gürtler  
PrioritynormalSeverityminorReproducibilityhave not tried
Status resolvedResolutionfixed 
Product VersionV1.01 
Target VersionV1.01 
Summary0009221: Handling of PDDescriptor from ProcessDataInput / ProcessDataOutput
Description

PDDescriptor is an optional variable in OPC UA model.

Depending on IO-Link Device, PDDescriptor for ProcessDataInput or ProcessDataOutput is not supported and
the OPC UA Server application receive an error response from the IO-Link Device.

OPC UA Server Application shall find out, if the PDDescriptor is available for this device by reading direct parameter page 1 (see screenshot)

This hint shall be added to the specification.

TagsNo tags attached.
Attached Files
DirectParameterPage1.JPG (131,575 bytes)   
DirectParameterPage1.JPG (131,575 bytes)   

Activities

Tobias Gürtler

2023-10-27 09:39

developer   ~0020250

Done in " OPC 30120 - UA Companion Specification for IO-Link 1.01.00 Draft V00.02_TG.docx"

Martin Lang

2024-02-16 10:29

manager   ~0020839

WG review ok.

Issue History

Date Modified Username Field Change
2023-10-27 09:22 Tobias Gürtler New Issue
2023-10-27 09:22 Tobias Gürtler Status new => assigned
2023-10-27 09:22 Tobias Gürtler Assigned To => Tobias Gürtler
2023-10-27 09:22 Tobias Gürtler File Added: DirectParameterPage1.JPG
2023-10-27 09:39 Tobias Gürtler Status assigned => feedback
2023-10-27 09:39 Tobias Gürtler Note Added: 0020250
2024-02-16 10:29 Martin Lang Status feedback => resolved
2024-02-16 10:29 Martin Lang Resolution open => fixed
2024-02-16 10:29 Martin Lang Note Added: 0020839