View Issue Details

IDProjectCategoryView StatusLast Update
000922230120: IO-Link[UA] IO-Link Wirelesspublic2023-10-27 14:10
ReporterMartin Lang Assigned To 
PrioritynormalSeverityminorReproducibilityhave not tried
Status newResolutionopen 
Summary0009222: Add ObjectType for IO-Link Wireless Bridge
Description

Define an ObjectType for IO-Link Wireless Bridge. The ObjectInstanceDeclaration should be placed below the IO-Link Wireless Port ObjectType with the modelling rule OptionalPlaceholder.

Currently, there is no clear definition from SMI on how to evaluate the Bridge Standalone Mode. There are no new IO-Link Master events that signal in which mode the Bridge/Port is running. The latest proposal from the SMI Working Group was to evaluate this by comparing VendorId and DeviceId, but this is not feasible in a real device in the field since some OPC UA IO-Link Masters already in the field do not know about newer Bridge VendorId/DeviceId.

The SMI specification should provide a generic way. Until a solution is provided, OPC UA for IO-Link cannot include this new ObjectType for Bridges.

TagsNo tags attached.

Relationships

related to 0008622 assignedDeepak Yadav Add IO-Link Wireless System Extensions to companion specification 

Activities

There are no notes attached to this issue.

Issue History

Date Modified Username Field Change
2023-10-27 14:09 Martin Lang New Issue
2023-10-27 14:09 Martin Lang Relationship added related to 0008622
2023-10-27 14:10 Martin Lang Description Updated