View Issue Details
ID | Project | Category | View Status | Date Submitted | Last Update |
---|---|---|---|---|---|
0009532 | 10000-015: Safety | Spec | public | 2024-04-30 13:45 | 2024-04-30 15:05 |
Reporter | Christian Eitner | Assigned To | Christian Eitner | ||
Priority | normal | Severity | major | Reproducibility | always |
Status | closed | Resolution | open | ||
Product Version | 1.05.04 RC1 | ||||
Target Version | 1.05.04 RC1 | ||||
Summary | 0009532: Definition of Macro <Use FSV> in Table 33 Incorrectly Manipulates "SAPI.NonSafetyData" Instead of "SAPI.SafetyData" | ||||
Description | See title. In the If statement, SAPI.SafetyData should be manipulated, not SAPI.NonSafetyData. | ||||
Additional Information | This was a misinterpretation of the pseudo code. The first line in the code does set SAPI.SafetyData to binary zero. The code in the If statement deals with the NonSafetyData exactly as is described in the second note. | ||||
Tags | No tags attached. | ||||
Commit Version | |||||
Date Modified | Username | Field | Change |
---|---|---|---|
2024-04-30 13:45 | Christian Eitner | New Issue | |
2024-04-30 13:45 | Christian Eitner | Status | new => assigned |
2024-04-30 13:45 | Christian Eitner | Assigned To | => Christian Eitner |
2024-04-30 13:46 | Christian Eitner | Summary | Definition of Macro <Use FSV> in Table 33 Incorrectly Sets "SAPI.NonSafetyData" to Binary Zero Instead of "SAPI.SafetyData" => Definition of Macro <Use FSV> in Table 33 Incorrectly Manipulates "SAPI.NonSafetyData" Instead of "SAPI.SafetyData" |
2024-04-30 15:05 | Christian Eitner | Status | assigned => closed |
2024-04-30 15:05 | Christian Eitner | Additional Information Updated |