Summary0007001: The severity of a limit Alarm
Description

The severity of an alarm is indicated by the value of the severity property in the BaseEventType. An instance of an alarm can be configured with a fixed value for this severity. In an advanced alarming system, this severity might be updated. For a Limit alarm, which has multiple states, each of which might have there own severity, there is only one bucket. This does not allow a value to be set, showing the default severity for each limit. Propose adding BaseSeverityHighHigh, BaseSeverityHigh, BaseSeverityLow, BaseSeverityLowLow Optional Properties to allow setting the default for each limit.

TagsNo tags attached.
Commit Version
Fix Due Date

Relationships

related to 0007386 closedRandy Armstrong NodeSets, XSDs and Generated Code The severity of a limit Alarm 

Activities

Paul Hunkar

2021-06-10 15:03

developer   ~0014543

Updated to add SeverityHighHigh, SeverityHigh, SeverityLow, SeverityLowLow

Randy Armstrong

2021-08-10 15:43

administrator   ~0014720

Reviewed Part9 1.05 DRAFT 9 in UA meeting.

Issue History

Date Modified Username Field Change
2021-06-10 12:35 Paul Hunkar New Issue
2021-06-10 15:01 Paul Hunkar Assigned To => Paul Hunkar
2021-06-10 15:01 Paul Hunkar Status new => assigned
2021-06-10 15:03 Paul Hunkar Status assigned => resolved
2021-06-10 15:03 Paul Hunkar Resolution open => fixed
2021-06-10 15:03 Paul Hunkar Fixed in Version => 1.05.00
2021-06-10 15:03 Paul Hunkar Note Added: 0014543
2021-08-10 15:43 Randy Armstrong Status resolved => closed
2021-08-10 15:43 Randy Armstrong Note Added: 0014720
2021-11-04 20:29 Jim Luth Issue cloned: 0007386
2021-11-04 20:29 Jim Luth Relationship added related to 0007386