View Issue Details

IDProjectCategoryView StatusLast Update
000194110000-006: Mappingspublic2012-05-08 19:56
ReporterJouni Aro Assigned ToRandy Armstrong  
PrioritynormalSeverityminorReproducibilityalways
Status closedResolutionfixed 
Product Version1.02 
Fixed in Version1.02 
Summary0001941: ExtraPadding not mentioned in p.48 message structure
Description

The following table (or equation in version RC1.02.09) requires also a mention about the ExtraPaddingSize, which is now added to Table 33:

MaxCertificateSize =
MessageChunkSize –
12 - // Header size
4 - // SecurityPolicyUriLength
SecurityPolicyUri - // UTF-8 encoded string
4 - // SenderCertificateLength
4 - // ReceiverCertificateThumbprintLength
20 - // ReceiverCertificateThumbprint
8 - // SequenceHeader size
1 - // Minimum body size
1 - // PaddingSize if present
Padding - // Padding if present
AsymmetricSignatureSize // If present

I also wonder how this affects older applications: are they still compatible with the new ones after this change?

TagsNo tags attached.
Commit Version
Fix Due Date

Activities

Randy Armstrong

2012-05-08 02:16

administrator   ~0003638

Added field to RC 1.02.10

Jim Luth

2012-05-08 19:56

administrator   ~0003655

Reviewed and accepted changes in telecon.

Issue History

Date Modified Username Field Change
2012-03-19 16:00 Jouni Aro New Issue
2012-03-27 16:28 Jim Luth Status new => assigned
2012-03-27 16:28 Jim Luth Assigned To => Randy Armstrong
2012-05-08 02:16 Randy Armstrong Status assigned => resolved
2012-05-08 02:16 Randy Armstrong Resolution open => fixed
2012-05-08 02:16 Randy Armstrong Note Added: 0003638
2012-05-08 19:56 Jim Luth Status resolved => closed
2012-05-08 19:56 Jim Luth Note Added: 0003655
2012-05-08 19:56 Jim Luth Fixed in Version => 1.02