View Issue Details

IDProjectCategoryView StatusLast Update
000426510000-004: ServicesSpecpublic2020-06-15 18:08
ReporterWolfgang Mahnke Assigned ToMatthias Damm  
PrioritynormalSeverityminorReproducibilityalways
Status closedResolutionfixed 
Summary0004265: Lifetime of ContinuationPoints in
Description

The lifetime of a ContinuationPoint is currently bound to a session (7.6 of Part 4). The services using a ContinuationPoint (Browse, Query, HistoryRead) can now also be called using the session-less service invocation.
It needs to be defined how ContinuationPoints are handled in that situation.

TagsNo tags attached.
Commit Version
Fix Due Date

Activities

Matthias Damm

2020-06-15 16:29

developer   ~0012294

Added the following clarification to 7.8 ContinuationPoint:
For Session-less Service invocations, the Server shall support at least the maximum number of ContinuationPoints it would allow for one Session.

Added in OPC 10000-4 - UA Specification Part 4 - Services Draft 1.05.08.docx

Jim Luth

2020-06-15 18:08

administrator   ~0012312

Agreed to changes edited in Virtual F2F.

Issue History

Date Modified Username Field Change
2018-04-27 07:09 Wolfgang Mahnke New Issue
2018-08-14 16:56 Jim Luth Assigned To => Matthias Damm
2018-08-14 16:56 Jim Luth Status new => assigned
2020-06-15 16:29 Matthias Damm Status assigned => resolved
2020-06-15 16:29 Matthias Damm Resolution open => fixed
2020-06-15 16:29 Matthias Damm Note Added: 0012294
2020-06-15 18:08 Jim Luth Status resolved => closed
2020-06-15 18:08 Jim Luth Fixed in Version => 1.05
2020-06-15 18:08 Jim Luth Note Added: 0012312