View Issue Details
| ID | Project | Category | View Status | Date Submitted | Last Update |
|---|---|---|---|---|---|
| 0004966 | 10000-009: Alarms and Conditions | Spec | public | 2019-08-21 18:08 | 2021-11-04 20:27 |
| Reporter | Jim Luth | Assigned To | Paul Hunkar | ||
| Priority | normal | Severity | minor | Reproducibility | have not tried |
| Status | closed | Resolution | fixed | ||
| Summary | 0004966: Alarm Deadband needs to be added to all limit and deviation alarms | ||||
| Description | Part 9 references alarm deadband in Figure 6 and in Annex E, but the feature is not included anywhere. The feature needs to be present on all limit alarms and all deviation alarms. | ||||
| Tags | No tags attached. | ||||
| Commit Version | |||||
| Fix Due Date | |||||
| related to | 0007385 | closed | Randy Armstrong | NodeSets, XSDs and Generated Code | Alarm Deadband needs to be added to all limit and deviation alarms |
|
|
Added Deadband properties for all limits in the limit AlarmType (from which all other types described in this issue are derived) |
|
|
Agreed to changes in virtual F2F. |
| Date Modified | Username | Field | Change |
|---|---|---|---|
| 2019-08-21 18:08 | Jim Luth | New Issue | |
| 2019-11-26 17:10 | Jim Luth | Assigned To | => Paul Hunkar |
| 2019-11-26 17:10 | Jim Luth | Status | new => assigned |
| 2019-12-26 06:23 | Paul Hunkar | Status | assigned => resolved |
| 2019-12-26 06:23 | Paul Hunkar | Resolution | open => fixed |
| 2019-12-26 06:23 | Paul Hunkar | Fixed in Version | => 1.05 |
| 2019-12-26 06:23 | Paul Hunkar | Note Added: 0011380 | |
| 2020-06-19 15:04 | Jim Luth | Status | resolved => closed |
| 2020-06-19 15:04 | Jim Luth | Note Added: 0012481 | |
| 2021-11-04 20:27 | Jim Luth | Issue cloned: 0007385 | |
| 2021-11-04 20:27 | Jim Luth | Relationship added | related to 0007385 |