View Issue Details

IDProjectCategoryView StatusLast Update
000589530120: IO-LinkImplementation Bugpublic2023-02-10 17:02
ReporterMartin Lang Assigned To 
PrioritynormalSeverityminorReproducibilityhave not tried
Status resolvedResolutionopen 
Summary0005895: Fix wrong value rank for output arguments ErrorType and Status
Description

Within the Nodeset file published at 2018-12-01T00:00:00, V1.0.
The Companion Specification defines Scalar as Output Argument. The Nodeset file uses OneDimension array.

  • ns=1;i=6116 --> Argument ErrorType + Status
  • ns=1;i=6121 --> Arguemnt ErrorType + Status
TagsNo tags attached.
Attached Files

Relationships

related to 0007416 confirmedDeepak Yadav Support for IO Link Wireless Extensions 

Activities

Joachim Stilz

2021-02-09 09:48

viewer   ~0013690

Will be corrected in Release 1.00.01.
ErrorType and Status are always scalar (ValueRank = -1).

Issue History

Date Modified Username Field Change
2020-08-14 14:24 Martin Lang New Issue
2020-08-14 14:24 Martin Lang File Added: Opc.Ua.IOLink.NodeSet2.xml
2021-02-09 09:48 Joachim Stilz Note Added: 0013690
2021-02-09 12:55 Joachim Stilz Status new => resolved
2021-02-09 12:55 Joachim Stilz Description Updated