View Issue Details
ID | Project | Category | View Status | Date Submitted | Last Update |
---|---|---|---|---|---|
0008291 | Part 84: UAFX Profiles | Spec | public | 2022-09-06 13:15 | 2022-10-18 13:06 |
Reporter | Georg Biehler | Assigned To | Bob Lattimer | ||
Priority | normal | Severity | minor | Reproducibility | have not tried |
Status | closed | Resolution | fixed | ||
Product Version | 1.00.00 RC3 | ||||
Fixed in Version | 1.00.00 Release | ||||
Summary | 0008291: Exposure of PubSub configuration model | ||||
Description | The exposure of the PubSub configuration model is optional. | ||||
Tags | No tags attached. | ||||
|
I recall a requirement (but couldn't find it) where a connection configuration based on either the offline descriptor or on online retrieved information shall be possible (should ask Paul Brooks for the MR). In addition, we have a statement in 6.16.3.2 that the ConnectionManager may generate the PubSubConfiguration. Both cases (online retrieval and CM generated PubSub) require the exposure of preconfigured DataSets. Thus an AutomationComponent having preconfigured DataSets has to expose the PublishSubscribe Object, including the mandatory items as required by Part14; these are Status, SupportedTransportProfiles, and the (maybe empty) PublishedDataSets folder. Side Note: We have a statement in Part81 that a FunctionalEntity may decide not to expose the ConnectionEndpoints. If an AutomationComponent does not support preconfigured DataSets or later preconfigured PubSub configuration elements, there is no need to expose the PubSub configuration, including the PublishSubscribe object. For the SKS an exposure of the configuration model (SecurityGroups, PubSubKeyPushTargets) including the Methods for configuration (i.e., AddSecurityGroup, AddPushTargert, ConnectSecurityGroups), if the SKS is not co-located with a ConnectionManager (in this case the CM may use vendor specific means to configure the SKS). |
|
best to handle this in ConformanceUnits |
|
We decided that preconfigured datasets should be exposed. This will require new conformance units that mandate support of the PublishSubscribe Object. |
|
UAFX Preconfigured Published Dataset and UAFX Preconfigured Subscribed Dataset conformance units were added. |
|
The additions were reviewed and approved in an AWG meeting. |
Date Modified | Username | Field | Change |
---|---|---|---|
2022-09-06 13:15 | Georg Biehler | New Issue | |
2022-09-07 07:45 | Georg Biehler | Assigned To | => Georg Biehler |
2022-09-07 07:45 | Georg Biehler | Status | new => assigned |
2022-09-07 08:05 | Georg Biehler | Note Added: 0017534 | |
2022-09-23 13:28 | Paul Hunkar | Project | Part 81: UAFX Connecting Devices and Information Model => Part 84: UAFX Profiles |
2022-09-23 13:28 | Paul Hunkar | Note Added: 0017833 | |
2022-10-18 11:32 | Greg Majcher | Note Added: 0018071 | |
2022-10-18 11:33 | Greg Majcher | Assigned To | Georg Biehler => Bob Lattimer |
2022-10-18 12:00 | Greg Majcher | Status | assigned => resolved |
2022-10-18 12:00 | Greg Majcher | Resolution | open => fixed |
2022-10-18 12:00 | Greg Majcher | Fixed in Version | => 1.00.00 Release |
2022-10-18 12:00 | Greg Majcher | Note Added: 0018073 | |
2022-10-18 13:06 | Greg Majcher | Status | resolved => closed |
2022-10-18 13:06 | Greg Majcher | Note Added: 0018078 |