View Issue Details
ID | Project | Category | View Status | Date Submitted | Last Update |
---|---|---|---|---|---|
0008306 | Part 84: UAFX Profiles | Spec | public | 2022-09-07 21:56 | 2022-09-14 14:07 |
Reporter | Bob Lattimer | Assigned To | Bob Lattimer | ||
Priority | normal | Severity | minor | Reproducibility | have not tried |
Status | closed | Resolution | fixed | ||
Product Version | 1.00.00 RC3 | ||||
Fixed in Version | 1.00.00 | ||||
Summary | 0008306: Minimum admin cycle time of 200 µs or smaller needs to be aligned with FA/PA requirements | ||||
Description | The 200 µs value for ports operating on 100 Mb/s in the UAFX EthernetBridgeQuantities Scheduled Traffic minCT ConformanceUnit was arrived at somewhat arbitrarily based on the 20 µs value for 1 Gb/s ports. These values should be changed if a requirement exists that goes above or below. | ||||
Tags | No tags attached. | ||||
|
Ken Lee took an action to research FA/PA requirements regarding cycle times which resulted in the attached email thread. Paul Brooks added to a separate branch of the email thread: All, the most important requirement is User Story 5941 and its child marketing requirements. For Motion the common cycle time (5942) is 2ms which was the lowest number that met everyone’s requirements and ACs with a minimum cycle time of 400ms (5945) must be supportable |