View Issue Details

IDProjectCategoryView StatusLast Update
0009544Part 81: UAFX Connecting Devices and Information ModelSpecpublic2024-10-25 12:20
ReporterJohannes Kempf Assigned ToPaul Hunkar  
PrioritynormalSeverityminorReproducibilityhave not tried
Status closedResolutionfixed 
Product Version1.00.02 
Fixed in Version1.00.03 
Summary0009544: Wrong reference between slots and assets
Description

Example D.2.3 uses "IsPhysicallyConnectedTo" references between slots and associated assets (e.g. CPUs and IOModules).
However section 6.3.5 SlotType definition states "Each Slot that has a module plugged into it shall have a HasAttachedComponent Reference".
This impacts many figures and the explaining text paragraphs of D.2.3.

TagsNo tags attached.

Activities

Paul Hunkar

2024-05-13 04:54

manager   ~0021182

The IsPhysicallyConnectedTo reference is legal to use (it is just a symmetric reference). The HasAttachedComponent hierarchical reference should be included in the figure to eliminate confusion or the statement in 6.3.5 requiring it should be removed - will have to discuss in a meeting.

Paul Hunkar

2024-10-25 12:20

manager   ~0021953

Updated spec to allow IsPhysicallyConnectedTo reference in addition to the HasPhysicalComponent

Paul Hunkar

2024-10-25 12:20

manager   ~0021954

agreed to change in meeting , closed issue

Issue History

Date Modified Username Field Change
2024-05-10 10:30 Johannes Kempf New Issue
2024-05-13 04:54 Paul Hunkar Note Added: 0021182
2024-06-07 12:44 Paul Hunkar Assigned To => Paul Hunkar
2024-06-07 12:44 Paul Hunkar Status new => assigned
2024-10-25 12:20 Paul Hunkar Status assigned => resolved
2024-10-25 12:20 Paul Hunkar Resolution open => fixed
2024-10-25 12:20 Paul Hunkar Fixed in Version => 1.00.03
2024-10-25 12:20 Paul Hunkar Note Added: 0021953
2024-10-25 12:20 Paul Hunkar Status resolved => closed
2024-10-25 12:20 Paul Hunkar Note Added: 0021954