0002699 | 10000-004: Services | Api Change | public | 2014-01-03 13:34 | 2014-12-19 18:52 |
Reporter | Rik Svendsen Rose | Assigned To | Matthias Damm | ||
Priority | normal | Severity | feature | Reproducibility | N/A |
Status | closed | Resolution | won't fix | ||
Summary | 0002699: TranslateBrowseNodeIds | ||||
Description | Hi Together with the two vendors is has been discovered that GENEISES64 uses "TranslateBrowseNodeIds" is causing the issue. The GENEISES64 uses TranslateBrowseNodeIds to make sure the syntax on the SCADA for all UA servers is the same. But The PLC take 4-5seconds to diliver 500 nodeids. If a main purpose of OPC UA is to get the server into the blackboxes, but still have the "niceness" on the client side, this needs to be improved. I recommend that the "TranslateBrowseNodeIds" for the specification be improved to "GetAllNodeIds". Allowing the OPC client to ask for a ArrayList og all String names and there IDs. Then it is done on connection to the the server from the client, and the client can handle it with low priority... BR Rik | ||||
Additional Information | Does the future of OPC UA include focus on smaller embedded devices. | ||||
Tags | No tags attached. | ||||
Commit Version | |||||
Fix Due Date | |||||
related to | 0002918 | assigned | Matthias Damm | Provide an alternative to Browse and TranslateBrowsePathsToNodeIds |
|
Please note. GetAllNodeIds may need to be only supported by NodeId Strings. BR Rik |
|
Here are some notes and questions regarding your request:<br> (1) The TranslateBrowsePathsToNodeIds handles already an array of nodes.<br> (Question:) Are you looking for an offline representation of the server address space?<br> (Note:) Any way of getting a NodeId from a path or getting a snapshot of the server address space can be very slow for dynamic address spaces where the server has no optimized access to this information. |
|
Discussion on phone conference:<br> |
|
Created a feature request for the discussed option that would resolve the issue. See related issue. |
|
Reviewed in Tuesday telecon and agreed to no-fix and close. |
Date Modified | Username | Field | Change |
---|---|---|---|
2014-01-03 13:34 | Rik Svendsen Rose | New Issue | |
2014-01-03 14:46 | Rik Svendsen Rose | Note Added: 0005225 | |
2014-08-28 13:49 |
|
Project | UA Server - Certification tests => Specifications |
2014-08-28 13:49 |
|
Category | (No Category) => Api Change |
2014-09-05 20:40 |
|
Project | Specifications => Feature Requests |
2014-10-20 08:49 | Matthias Damm | Project | Feature Requests => 10000-004: Services |
2014-10-20 08:57 | Matthias Damm | Note Added: 0005569 | |
2014-10-20 08:58 | Matthias Damm | Note Edited: 0005569 | |
2014-11-17 20:56 | Matthias Damm | Assigned To | => Matthias Damm |
2014-11-17 20:56 | Matthias Damm | Status | new => assigned |
2014-12-16 13:15 | Matthias Damm | Note Edited: 0005569 | |
2014-12-16 17:22 | Matthias Damm | Note Added: 0005693 | |
2014-12-16 18:05 | Matthias Damm | Relationship added | related to 0002918 |
2014-12-16 18:06 | Matthias Damm | Note Added: 0005696 | |
2014-12-16 18:06 | Matthias Damm | Status | assigned => resolved |
2014-12-16 18:06 | Matthias Damm | Resolution | open => won't fix |
2014-12-19 18:52 | Jim Luth | Note Added: 0005704 | |
2014-12-19 18:52 | Jim Luth | Status | resolved => closed |